Filtered by vendor Siemens
Subscriptions
Total
2246 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2017-2685 | 1 Siemens | 3 Sinumerik Integrate Access Mymachine\/ethernet, Sinumerik Integrate Operate Client, Sinumerik Operate | 2025-04-20 | N/A |
| Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack. | ||||
| CVE-2017-9944 | 1 Siemens | 2 7kt Pac1200 Data Manager, 7kt Pac1200 Data Manager Firmware | 2025-04-20 | N/A |
| A vulnerability has been identified in Siemens 7KT PAC1200 data manager (7KT1260) in all versions < V2.03. The integrated web server (port 80/tcp) of the affected devices could allow an unauthenticated remote attacker to perform administrative operations over the network. | ||||
| CVE-2017-2684 | 1 Siemens | 1 Simatic Logon | 2025-04-20 | N/A |
| Siemens SIMATIC Logon prior to V1.5 SP3 Update 2 could allow an attacker with knowledge of a valid user name, and physical or network access to the affected system, to bypass the application-level authentication. | ||||
| CVE-2017-2686 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | N/A |
| Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability that could allow an authenticated user to read arbitrary files through the web interface at port 10000/TCP and access sensitive information. | ||||
| CVE-2017-2682 | 1 Siemens | 1 Ruggedcom Network Management Software | 2025-04-20 | N/A |
| The Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could allow a remote attacker to perform a Cross-Site Request Forgery (CSRF) attack, potentially allowing an attacker to execute administrative operations, provided the targeted user has an active session and is induced to trigger a malicious request. | ||||
| CVE-2021-37185 | 1 Siemens | 95 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 92 more | 2025-04-18 | 7.5 High |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations. | ||||
| CVE-2021-37204 | 1 Siemens | 95 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 92 more | 2025-04-18 | 7.5 High |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations. | ||||
| CVE-2021-37205 | 1 Siemens | 95 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 92 more | 2025-04-18 | 7.5 High |
| A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations. | ||||
| CVE-2023-51439 | 1 Siemens | 2 Jt2go, Teamcenter Visualization | 2025-04-17 | 7.8 High |
| A vulnerability has been identified in JT2Go (All versions < V14.3.0.6), Teamcenter Visualization V13.3 (All versions < V13.3.0.13), Teamcenter Visualization V14.1 (All versions < V14.1.0.12), Teamcenter Visualization V14.2 (All versions < V14.2.0.9), Teamcenter Visualization V14.3 (All versions < V14.3.0.6). The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted CGM files. This could allow an attacker to execute code in the context of the current process. | ||||
| CVE-2022-2069 | 1 Siemens | 2 Jt2go, Teamcenter Visualization | 2025-04-16 | 7.8 High |
| The APDFL.dll in Siemens JT2Go prior to V13.3.0.5 and Siemens Teamcenter Visualization prior to V14.0.0.2 contains an out of bounds write past the fixed-length heap-based buffer while parsing specially crafted PDF files. This could allow an attacker to execute code in the context of the current process. | ||||
| CVE-2014-2731 | 1 Siemens | 1 Sinema Server | 2025-04-12 | N/A |
| Multiple unspecified vulnerabilities in the integrated web server in Siemens SINEMA Server before 12 SP1 allow remote attackers to execute arbitrary code via HTTP traffic to port (1) 4999 or (2) 80. | ||||
| CVE-2014-4686 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | N/A |
| The Project administration application in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, has a hardcoded encryption key, which allows remote attackers to obtain sensitive information by extracting this key from another product installation and then employing this key during the sniffing of network traffic on TCP port 1030. | ||||
| CVE-2016-6486 | 1 Siemens | 1 Sinema Server | 2025-04-12 | N/A |
| Siemens SINEMA Server uses weak permissions for the application folder, which allows local users to gain privileges via unspecified vectors. | ||||
| CVE-2014-2257 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets. | ||||
| CVE-2014-4682 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | N/A |
| The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request. | ||||
| CVE-2014-2732 | 1 Siemens | 1 Sinema Server | 2025-04-12 | N/A |
| Multiple directory traversal vulnerabilities in the integrated web server in Siemens SINEMA Server before 12 SP1 allow remote attackers to access arbitrary files via HTTP traffic to port (1) 4999 or (2) 80. | ||||
| CVE-2014-2733 | 1 Siemens | 1 Sinema Server | 2025-04-12 | N/A |
| Siemens SINEMA Server before 12 SP1 allows remote attackers to cause a denial of service (web-interface outage) via crafted HTTP requests to port (1) 4999 or (2) 80. | ||||
| CVE-2015-4174 | 1 Siemens | 1 Climatix Bacnet\/ip | 2025-04-12 | N/A |
| Cross-site scripting (XSS) vulnerability in the integrated web server on the Siemens Climatix BACnet/IP communication module with firmware before 10.34 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
| CVE-2016-8561 | 1 Siemens | 2 Simatic Cp 1543-1, Simatic Cp 1543-1 Firmware | 2025-04-12 | N/A |
| A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Users with elevated privileges to TIA-Portal and project data on the engineering station could possibly get privileged access on affected devices. | ||||
| CVE-2014-2256 | 1 Siemens | 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more | 2025-04-12 | N/A |
| Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets, a different vulnerability than CVE-2014-2257. | ||||