Show plain JSON{"configurations": [{"nodes": [{"cpeMatch": [{"criteria": "cpe:2.3:a:inductiveautomation:ignition:*:*:*:*:*:*:*:*", "matchCriteriaId": "23FE7E78-2B70-4A4F-9B10-94C3F64CB5F8", "versionEndExcluding": "8.1.26", "vulnerable": true}], "negate": false, "operator": "OR"}]}], "cveTags": [], "descriptions": [{"lang": "en", "value": "Inductive Automation Ignition OPC UA Quick Client Cross-Site Scripting Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Inductive Automation Ignition. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file.\n\nThe specific flaw exists within the handling of the id parameter provided to the Inductive Automation Ignition web interface. The issue results from the lack of proper validation of user-supplied data, which can lead to the injection of an arbitrary script. An attacker can leverage this vulnerability to execute arbitrary code in the context of SYSTEM. Was ZDI-CAN-20355."}, {"lang": "es", "value": "Vulnerabilidad de ejecuci\u00f3n remota de c\u00f3digo de Cross-Site Scripting del cliente r\u00e1pido OPC UA de encendido de automatizaci\u00f3n inductiva. Esta vulnerabilidad permite a atacantes remotos ejecutar c\u00f3digo arbitrario en las instalaciones afectadas de Inductive Automation Ignition. Se requiere la interacci\u00f3n del usuario para aprovechar esta vulnerabilidad, ya que el objetivo debe visitar una p\u00e1gina maliciosa o abrir un archivo malicioso. La falla espec\u00edfica existe en el manejo del par\u00e1metro id proporcionado a la interfaz web de Inductive Automation Ignition. El problema se debe a la falta de validaci\u00f3n adecuada de los datos proporcionados por el usuario, lo que puede llevar a la inyecci\u00f3n de un script arbitrario. Un atacante puede aprovechar esta vulnerabilidad para ejecutar c\u00f3digo arbitrario en el contexto de SYSTEM. Era ZDI-CAN-20355."}], "id": "CVE-2023-38121", "lastModified": "2025-03-12T14:32:50.177", "metrics": {"cvssMetricV30": [{"cvssData": {"attackComplexity": "HIGH", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 8.3, "baseSeverity": "HIGH", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "CHANGED", "userInteraction": "REQUIRED", "vectorString": "CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H", "version": "3.0"}, "exploitabilityScore": 1.6, "impactScore": 6.0, "source": "zdi-disclosures@trendmicro.com", "type": "Secondary"}], "cvssMetricV31": [{"cvssData": {"attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 9.0, "baseSeverity": "CRITICAL", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "privilegesRequired": "LOW", "scope": "CHANGED", "userInteraction": "REQUIRED", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:H", "version": "3.1"}, "exploitabilityScore": 2.3, "impactScore": 6.0, "source": "nvd@nist.gov", "type": "Primary"}]}, "published": "2024-05-03T02:15:56.377", "references": [{"source": "zdi-disclosures@trendmicro.com", "tags": ["Vendor Advisory"], "url": "https://inductiveautomation.com/blog/inductive-automation-participates-in-pwn2own-to-strengthen-ignition-security"}, {"source": "zdi-disclosures@trendmicro.com", "tags": ["Third Party Advisory"], "url": "https://www.zerodayinitiative.com/advisories/ZDI-23-1012/"}, {"source": "af854a3a-2127-422b-91ae-364da2661108", "tags": ["Vendor Advisory"], "url": "https://inductiveautomation.com/blog/inductive-automation-participates-in-pwn2own-to-strengthen-ignition-security"}, {"source": "af854a3a-2127-422b-91ae-364da2661108", "tags": ["Third Party Advisory"], "url": "https://www.zerodayinitiative.com/advisories/ZDI-23-1012/"}], "sourceIdentifier": "zdi-disclosures@trendmicro.com", "vulnStatus": "Analyzed", "weaknesses": [{"description": [{"lang": "en", "value": "CWE-79"}], "source": "zdi-disclosures@trendmicro.com", "type": "Secondary"}, {"description": [{"lang": "en", "value": "CWE-79"}], "source": "nvd@nist.gov", "type": "Primary"}]}