Filtered by vendor Rockwellautomation
Subscriptions
Filtered by product Compact Guardlogix 5380
Subscriptions
Total
10 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2026-9636 | 1 Rockwellautomation | 5 1756-en4tr, Compact Guardlogix 5380, Compactlogix 5380 and 2 more | 2026-11-11 | N/A |
| A security issue exists within CompactLogix® 5380, ControlLogix® 5580, and EN4 communication modules related to CIP Security certificate revocation handling. The security issue stems from the controller failing to properly reject certificates signed by an intermediate certificate that has been revoked via a Certificate Revocation List (CRL). This could allow a network-based attacker to establish a connection using a certificate that should be untrusted, potentially bypassing CIP Security protections. | ||||
| CVE-2021-22681 | 1 Rockwellautomation | 20 Compact Guardlogix 5370, Compact Guardlogix 5380, Compactlogix 1768 and 17 more | 2026-03-06 | 9.8 Critical |
| Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. | ||||
| CVE-2022-1159 | 1 Rockwellautomation | 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more | 2025-04-16 | 7.7 High |
| Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user. | ||||
| CVE-2022-1161 | 1 Rockwellautomation | 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more | 2025-04-16 | 10 Critical |
| An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. | ||||
| CVE-2022-1797 | 1 Rockwellautomation | 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more | 2025-04-16 | 6.8 Medium |
| A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. | ||||
| CVE-2022-3157 | 1 Rockwellautomation | 12 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 9 more | 2025-04-16 | 8.6 High |
| A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS). | ||||
| CVE-2022-3752 | 1 Rockwellautomation | 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more | 2025-04-16 | 8.6 High |
| An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation. | ||||
| CVE-2024-5659 | 1 Rockwellautomation | 12 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 and 9 more | 2024-11-21 | 6.5 Medium |
| Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised. | ||||
| CVE-2024-3493 | 1 Rockwellautomation | 16 1756-en4tr, 1756-en4tr Firmware, Compact Guardlogix 5380 and 13 more | 2024-11-21 | 8.6 High |
| A specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. | ||||
| CVE-2024-8626 | 1 Rockwellautomation | 12 1756-en4tr, 1756-en4tr Firmware, Compact Guardlogix 5380 and 9 more | 2024-10-10 | 7.5 High |
| Due to a memory leak, a denial-of-service vulnerability exists in the Rockwell Automation affected products. A malicious actor could exploit this vulnerability by performing multiple actions on certain web pages of the product causing the affected products to become fully unavailable and require a power cycle to recover. | ||||
Page 1 of 1.