Filtered by vendor Rockwellautomation
Subscriptions
Total
365 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2014-5424 | 1 Rockwellautomation | 1 Connected Components Workbench | 2025-04-12 | N/A |
| Rockwell Automation Connected Components Workbench (CCW) before 7.00.00 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via an invalid property value to an ActiveX control that was built with an outdated compiler. | ||||
| CVE-2016-5814 | 1 Rockwellautomation | 5 Rslogix 500 Professional Edition, Rslogix 500 Standard Edition, Rslogix 500 Starter Edition and 2 more | 2025-04-12 | N/A |
| Buffer overflow in Rockwell Automation RSLogix Micro Starter Lite, RSLogix Micro Developer, RSLogix 500 Starter Edition, RSLogix 500 Standard Edition, and RSLogix 500 Professional Edition allows remote attackers to execute arbitrary code via a crafted RSS project file. | ||||
| CVE-2016-4531 | 1 Rockwellautomation | 1 Factorytalk Energrymetrix | 2025-04-12 | N/A |
| Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 does not invalidate credentials upon a logout action, which makes it easier for remote attackers to obtain access by leveraging an unattended workstation. | ||||
| CVE-2016-4522 | 1 Rockwellautomation | 1 Factorytalk Energrymetrix | 2025-04-12 | N/A |
| SQL injection vulnerability in Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 allows remote attackers to execute arbitrary SQL commands via unspecified vectors. | ||||
| CVE-2015-6492 | 1 Rockwellautomation | 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware | 2025-04-12 | N/A |
| Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote attackers to cause a denial of service (memory corruption and device crash) via a crafted HTTP request. | ||||
| CVE-2012-4715 | 1 Rockwellautomation | 1 Rslinx Enterprise | 2025-04-11 | N/A |
| Buffer overflow in LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (daemon crash) or possibly execute arbitrary code via a UDP packet with a certain integer length value that is (1) too large or (2) too small, leading to improper handling by Logger.dll. | ||||
| CVE-2012-0221 | 1 Rockwellautomation | 2 Factorytalk, Rslogix 5000 | 2025-04-11 | N/A |
| The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 does not properly handle the return value from an unspecified function, which allows remote attackers to cause a denial of service (service outage) via a crafted packet. | ||||
| CVE-2012-4690 | 1 Rockwellautomation | 3 Ab Micrologix Controller, Plc-5 Controller, Slc 500 Controller | 2025-04-11 | N/A |
| Rockwell Automation Allen-Bradley MicroLogix controller 1100, 1200, 1400, and 1500; SLC 500 controller platform; and PLC-5 controller platform, when Static status is not enabled, allow remote attackers to cause a denial of service via messages that trigger modification of status bits. | ||||
| CVE-2011-2957 | 1 Rockwellautomation | 1 Factorytalk Diagnostics Viewer | 2025-04-11 | N/A |
| Unspecified vulnerability in Rockwell Automation FactoryTalk Diagnostics Viewer before V2.30.00 (CPR9 SR3) allows local users to execute arbitrary code via a crafted FactoryTalk Diagnostics Viewer (.ftd) configuration file, which triggers memory corruption. | ||||
| CVE-2011-2530 | 1 Rockwellautomation | 2 Eds Hardware Installation Tool, Rslinx | 2025-04-11 | N/A |
| Buffer overflow in RSEds.dll in RSHWare.exe in the EDS Hardware Installation Tool 1.0.5.1 and earlier in Rockwell Automation RSLinx Classic before 2.58 allows user-assisted remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a malformed .eds file. | ||||
| CVE-2012-4713 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2025-04-11 | N/A |
| Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value. | ||||
| CVE-2012-4695 | 1 Rockwellautomation | 1 Rslinx Enterprise | 2025-04-11 | N/A |
| LogReceiver.exe in Rockwell Automation RSLinx Enterprise CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage) via a zero-byte UDP packet that is not properly handled by Logger.dll. | ||||
| CVE-2010-2965 | 2 Rockwellautomation, Windriver | 3 1756-enbt\/a, 1756-enbt\/a Firmware, Vxworks | 2025-04-11 | N/A |
| The WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on the Rockwell Automation 1756-ENBT series A with firmware 3.2.6 and 3.6.1 and other products, allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185, a related issue to CVE-2005-3804. | ||||
| CVE-2009-3739 | 1 Rockwellautomation | 2 Ab Micrologix Controller 1100, Ab Micrologix Controller 1400 | 2025-04-11 | N/A |
| Multiple unspecified vulnerabilities on the Rockwell Automation AB Micrologix 1100 and 1400 controllers allow remote attackers to obtain privileged access or cause a denial of service (halt) via unknown vectors. | ||||
| CVE-2012-4714 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2025-04-11 | N/A |
| Integer overflow in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a large integer value. | ||||
| CVE-2011-3489 | 1 Rockwellautomation | 1 Rslogix | 2025-04-11 | N/A |
| RnaUtility.dll in RsvcHost.exe 2.30.0.23 in Rockwell RSLogix 19 and earlier allows remote attackers to cause a denial of service (crash) via a crafted rna packet with a long string to TCP port 4446 that triggers (1) "a memset zero overflow" or (2) an out-of-bounds read, related to improper handling of a 32-bit size field. | ||||
| CVE-2012-0222 | 1 Rockwellautomation | 2 Factorytalk, Rslogix 5000 | 2025-04-11 | N/A |
| The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 allows remote attackers to cause a denial of service (out-of-bounds read) via a crafted packet. | ||||
| CVE-2022-3156 | 1 Rockwellautomation | 1 Studio 5000 Logix Emulate | 2025-04-10 | 7.8 High |
| A remote code execution vulnerability exists in Rockwell Automation Studio 5000 Logix Emulate software. Users are granted elevated permissions on certain product services when the software is installed. Due to this misconfiguration, a malicious user could potentially achieve remote code execution on the targeted software. | ||||
| CVE-2009-0472 | 1 Rockwellautomation | 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge | 2025-04-09 | N/A |
| Multiple cross-site scripting (XSS) vulnerabilities in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allow remote attackers to inject arbitrary web script or HTML via unspecified vectors. | ||||
| CVE-2009-0474 | 1 Rockwellautomation | 1 Controllogix 1756-enbt\/a Ethernet\/ Ip Bridge | 2025-04-09 | N/A |
| The web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to obtain "internal web page information" and "internal information about the module" via unspecified vectors. NOTE: this may overlap CVE-2002-1603. | ||||