Filtered by vendor Rockwellautomation
Subscriptions
Total
415 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2019-25276 | 1 Rockwellautomation | 2 Factorytalk Activation, Studio | 2026-04-15 | 7.8 High |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. | ||||
| CVE-2025-11084 | 1 Rockwellautomation | 1 Factorytalk | 2026-04-15 | N/A |
| A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period. | ||||
| CVE-2025-13824 | 1 Rockwellautomation | 3 Micro820, Micro850, Micro870 | 2026-04-15 | N/A |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. | ||||
| CVE-2024-7567 | 1 Rockwellautomation | 2 Micro850 Firmware, Micro870 Firmware | 2026-04-15 | N/A |
| A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration. | ||||
| CVE-2025-7353 | 1 Rockwellautomation | 1 Controllogix | 2026-04-15 | N/A |
| A security issue exists due to the web-based debugger agent enabled on Rockwell Automation ControlLogix® Ethernet Modules. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow. | ||||
| CVE-2024-6079 | 1 Rockwellautomation | 1 Emulate3d | 2026-04-15 | N/A |
| A vulnerability exists in the Rockwell Automation Emulate3D™, which could be leveraged to execute a DLL Hijacking attack. The application loads shared libraries, which are readable and writable by any user. If exploited, a malicious user could leverage a malicious dll and perform a remote code execution attack. | ||||
| CVE-2024-9412 | 1 Rockwellautomation | 1 Verve Asset Manager | 2026-04-15 | N/A |
| An improper authorization vulnerability exists in the Rockwell Automation affected products that could allow an unauthorized user to sign in. While removal of all role mappings is unlikely, it could occur in the case of unexpected or accidental removal by the administrator. If exploited, an unauthorized user could access data they previously but should no longer have access to. | ||||
| CVE-2025-9368 | 1 Rockwellautomation | 1 432es-ig3 Series A | 2026-04-15 | N/A |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. | ||||
| CVE-2025-7693 | 1 Rockwellautomation | 1 Micro800 | 2026-04-15 | N/A |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. | ||||
| CVE-2025-7350 | 1 Rockwellautomation | 1 Stratix | 2026-04-15 | N/A |
| A security issue affecting multiple Cisco devices also directly impacts Stratix® 5410, 5700, and 8000 devices. This can lead to remote code execution by uploading and running malicious configurations without authentication. | ||||
| CVE-2025-9036 | 1 Rockwellautomation | 1 Factorytalk Action Manager | 2026-04-15 | N/A |
| A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection. | ||||
| CVE-2025-14376 | 1 Rockwellautomation | 1 Verve Asset Manager | 2026-04-15 | N/A |
| A security issue was discovered within the legacy ADI server component of Verve Asset Manager, caused by plaintext secrets stored in environment variables on the ADI server. This component has been retired and has been optional since the 1.36 release in 2024. | ||||
| CVE-2024-10944 | 1 Rockwellautomation | 1 Factorytalk Updater | 2026-04-15 | 8.4 High |
| A Remote Code Execution vulnerability exists in the affected product. The vulnerability requires a high level of permissions and exists due to improper input validation resulting in the possibility of a malicious Updated Agent being deployed. | ||||
| CVE-2025-9041 | 1 Rockwellautomation | 1 Flex 5000 Io | 2026-04-15 | N/A |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. | ||||
| CVE-2025-7773 | 1 Rockwellautomation | 1 Armorblock 5000 Io | 2026-04-15 | N/A |
| A security issue exists within the 5032 16pt Digital Configurable module’s web server. The web server’s session number increments at an interval that correlates to the last two consecutive sign in session interval, making it predictable. | ||||
| CVE-2021-22681 | 1 Rockwellautomation | 20 Compact Guardlogix 5370, Compact Guardlogix 5380, Compactlogix 1768 and 17 more | 2026-03-06 | 9.8 Critical |
| Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. | ||||
| CVE-2025-7025 | 1 Rockwellautomation | 1 Arena | 2026-02-26 | 7.8 High |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. | ||||
| CVE-2025-7032 | 1 Rockwellautomation | 1 Arena | 2026-02-26 | 7.8 High |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. | ||||
| CVE-2025-7033 | 1 Rockwellautomation | 2 Arena, Arena Simulation | 2026-02-26 | 7.8 High |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. | ||||
| CVE-2023-5909 | 4 Ge, Ptc, Rockwellautomation and 1 more | 8 Industrial Gateway Server, Keepserverex, Opc-aggregator and 5 more | 2026-02-25 | 7.5 High |
| KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect. | ||||