Filtered by vendor Schneider-electric
Subscriptions
Total
768 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2017-7966 | 1 Schneider-electric | 1 Somachine | 2025-04-20 | N/A |
A DLL Hijacking vulnerability in the programming software in Schneider Electric's SoMachine HVAC v2.1.0 allows a remote attacker to execute arbitrary code on the targeted system. The vulnerability exists due to the improper loading of a DLL. | ||||
CVE-2017-9627 | 1 Schneider-electric | 1 Wonderware Archestra Logger | 2025-04-20 | 8.6 High |
An Uncontrolled Resource Consumption issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The uncontrolled resource consumption vulnerability could allow an attacker to exhaust the memory resources of the machine, causing a denial of service. | ||||
CVE-2017-7971 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate. | ||||
CVE-2017-7972 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to escape out of remote PowerSCADA Anywhere applications and launch other processes. | ||||
CVE-2017-7965 | 1 Schneider-electric | 1 Somachine Hvac | 2025-04-20 | 7.3 High |
A buffer overflow vulnerability exists in Programming Software executable AlTracePrint.exe, in Schneider Electric's SoMachine HVAC v2.1.0 for Modicon M171/M172 Controller. | ||||
CVE-2016-8352 | 1 Schneider-electric | 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more | 2025-04-20 | N/A |
An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code. | ||||
CVE-2016-5809 | 1 Schneider-electric | 6 Ion5000, Ion7300, Ion7500 and 3 more | 2025-04-20 | N/A |
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved. | ||||
CVE-2017-6019 | 1 Schneider-electric | 2 Conext Combox 865-1058, Conext Combox 865-1058 Firmware | 2025-04-20 | N/A |
An issue was discovered in Schneider Electric Conext ComBox, model 865-1058, all firmware versions prior to V3.03 BN 830. A series of rapid requests to the device may cause it to reboot. | ||||
CVE-2017-6026 | 1 Schneider-electric | 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more | 2025-04-20 | 9.1 Critical |
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised. | ||||
CVE-2017-6033 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2025-04-20 | N/A |
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path. | ||||
CVE-2017-5155 | 1 Schneider-electric | 1 Wonderware Historian | 2025-04-20 | N/A |
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well. | ||||
CVE-2017-13997 | 1 Schneider-electric | 2 Wonderware Indusoft Web Studio, Wonderware Intouch | 2025-04-20 | N/A |
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server. | ||||
CVE-2017-14024 | 1 Schneider-electric | 2 Wonderware Indusoft Web Studio, Wonderware Intouch | 2025-04-20 | N/A |
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges. | ||||
CVE-2016-5815 | 1 Schneider-electric | 6 Ion5000, Ion7300, Ion7500 and 3 more | 2025-04-20 | N/A |
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. | ||||
CVE-2017-7973 | 1 Schneider-electric | 1 U.motion Builder | 2025-04-20 | N/A |
A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database. | ||||
CVE-2016-8367 | 1 Schneider-electric | 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more | 2025-04-20 | 5.3 Medium |
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. | ||||
CVE-2017-6017 | 1 Schneider-electric | 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more | 2025-04-20 | N/A |
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. | ||||
CVE-2017-5178 | 1 Schneider-electric | 3 Tableau Desktop, Tableau Server, Wonderware Intelligence | 2025-04-20 | N/A |
An issue was discovered in Schneider Electric Tableau Server/Desktop Versions 7.0 to 10.1.3 in Wonderware Intelligence Versions 2014R3 and prior. These versions contain a system account that is installed by default. The default system account is difficult to configure with non-default credentials after installation, and changing the default credentials in the embedded Tableau Server is not documented. If Tableau Server is used with Windows integrated security (Active Directory), the software is not vulnerable. However, when Tableau Server is used with local authentication mode, the software is vulnerable. The default system account could be used to gain unauthorized access. | ||||
CVE-2017-7575 | 1 Schneider-electric | 2 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware | 2025-04-20 | N/A |
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded. | ||||
CVE-2017-7689 | 1 Schneider-electric | 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware | 2025-04-20 | 9.8 Critical |
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0. |