Filtered by vendor Schneider-electric Subscriptions
Total 765 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2017-6032 1 Schneider-electric 2 Modbus, Modbus Firmware 2025-04-20 N/A
A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks.
CVE-2017-6033 1 Schneider-electric 1 Interactive Graphical Scada System 2025-04-20 N/A
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path.
CVE-2017-6034 1 Schneider-electric 2 Modbus, Modbus Firmware 2025-04-20 N/A
An Authentication Bypass by Capture-Replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.
CVE-2017-5157 2 Schneider-electric, Schneider Electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 N/A
An issue was discovered in Schneider Electric homeLYnk Controller, LSS100100, all versions prior to V1.5.0. The homeLYnk controller is susceptible to a cross-site scripting attack. User inputs can be manipulated to cause execution of JavaScript code.
CVE-2016-8352 1 Schneider-electric 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more 2025-04-20 N/A
An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code.
CVE-2016-8374 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 7.5 High
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker may be able to disrupt a targeted web server, resulting in a denial of service because of UNCONTROLLED RESOURCE CONSUMPTION.
CVE-2016-5809 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2025-04-20 N/A
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved.
CVE-2016-5818 1 Schneider-electric 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware 2025-04-20 N/A
An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device.
CVE-2017-5178 1 Schneider-electric 3 Tableau Desktop, Tableau Server, Wonderware Intelligence 2025-04-20 N/A
An issue was discovered in Schneider Electric Tableau Server/Desktop Versions 7.0 to 10.1.3 in Wonderware Intelligence Versions 2014R3 and prior. These versions contain a system account that is installed by default. The default system account is difficult to configure with non-default credentials after installation, and changing the default credentials in the embedded Tableau Server is not documented. If Tableau Server is used with Windows integrated security (Active Directory), the software is not vulnerable. However, when Tableau Server is used with local authentication mode, the software is vulnerable. The default system account could be used to gain unauthorized access.
CVE-2016-5815 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2025-04-20 N/A
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes.
CVE-2016-8354 1 Schneider-electric 1 Unity Pro 2025-04-20 N/A
An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions.
CVE-2016-8367 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 5.3 Medium
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack.
CVE-2017-13997 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
CVE-2017-14024 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2025-04-20 N/A
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.
CVE-2017-5155 1 Schneider-electric 1 Wonderware Historian 2025-04-20 N/A
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well.
CVE-2017-7907 1 Schneider-electric 1 Wonderware Historian Client 2025-04-20 N/A
An Improper XML Parser Configuration issue was discovered in Schneider Electric Wonderware Historian Client 2014 R2 SP1 and prior. An improperly restricted XML parser (with improper restriction of XML external entity reference, or XXE) may allow an attacker to enter malicious input through the application which could cause a denial of service or disclose file contents from a server or connected network.
CVE-2017-7969 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 N/A
A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack.
CVE-2017-9961 1 Schneider-electric 1 Pro-face Gp Pro Ex 2025-04-20 N/A
A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process.
CVE-2020-25178 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 7.5 High
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
CVE-2020-25182 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2025-04-16 6.7 Medium
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.