Filtered by vendor Schneider-electric
Subscriptions
Total
765 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2022-24312 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2024-11-21 | 9.8 Critical |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause modification of an existing file by adding at end of file or create a new file in the context of the Data Server potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | ||||
CVE-2022-24311 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2024-11-21 | 9.8 Critical |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause modification of an existing file by inserting at beginning of file or create a new file in the context of the Data Server potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | ||||
CVE-2022-24310 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2024-11-21 | 9.8 Critical |
A CWE-190: Integer Overflow or Wraparound vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | ||||
CVE-2022-22813 | 1 Schneider-electric | 66 Easergy P141, Easergy P141 Firmware, Easergy P142 and 63 more | 2024-11-21 | 9.8 Critical |
A CWE-798: Use of Hard-coded Credentials vulnerability exists. If an attacker were to obtain the TLS cryptographic key and take active control of the Courier tunneling communication network, they could potentially observe and manipulate traffic associated with product configuration. | ||||
CVE-2022-22812 | 1 Schneider-electric | 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more | 2024-11-21 | 6.1 Medium |
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause a web session compromise when an attacker injects and then executes arbitrary malicious JavaScript code inside the target browser. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior) | ||||
CVE-2022-22811 | 1 Schneider-electric | 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more | 2024-11-21 | 8.1 High |
A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists that could induce users to perform unintended actions, leading to the override of the system�s configurations when an attacker persuades a user to visit a rogue website. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior) | ||||
CVE-2022-22810 | 1 Schneider-electric | 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more | 2024-11-21 | 9.8 Critical |
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow an attacker to manipulate the admin after numerous attempts at guessing credentials. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior) | ||||
CVE-2022-22809 | 1 Schneider-electric | 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more | 2024-11-21 | 5.3 Medium |
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow modifications of the touch configurations in an unauthorized manner when an attacker attempts to modify the touch configurations. Affected Product: spaceLYnk (V2.6.2 and prior), Wiser for KNX (formerly homeLYnk) (V2.6.2 and prior), fellerLYnk (V2.6.2 and prior) | ||||
CVE-2022-22808 | 1 Schneider-electric | 14 Hmibscea53d1edb, Hmibscea53d1edb Firmware, Hmibscea53d1edl and 11 more | 2024-11-21 | 8.8 High |
A CWE-352: Cross-Site Request Forgery (CSRF) exists that could cause a remote attacker to gain unauthorized access to the product when conducting cross-domain attacks based on same-origin policy or cross-site request forgery protections bypass. Affected Product: EcoStruxure EV Charging Expert (formerly known as EVlink Load Management System): (HMIBSCEA53D1EDB, HMIBSCEA53D1EDS, HMIBSCEA53D1EDM, HMIBSCEA53D1EDL, HMIBSCEA53D1ESS, HMIBSCEA53D1ESM, HMIBSCEA53D1EML) (All Versions prior to SP8 (Version 01) V4.0.0.13) | ||||
CVE-2022-22807 | 1 Schneider-electric | 14 Hmibscea53d1edb, Hmibscea53d1edb Firmware, Hmibscea53d1edl and 11 more | 2024-11-21 | 7.4 High |
A CWE-1021 Improper Restriction of Rendered UI Layers or Frames vulnerability exists that could cause unintended modifications of the product settings or user accounts when deceiving the user to use the web interface rendered within iframes. Affected Product: EcoStruxure EV Charging Expert (formerly known as EVlink Load Management System): (HMIBSCEA53D1EDB, HMIBSCEA53D1EDS, HMIBSCEA53D1EDM, HMIBSCEA53D1EDL, HMIBSCEA53D1ESS, HMIBSCEA53D1ESM, HMIBSCEA53D1EML) (All Versions prior to SP8 (Version 01) V4.0.0.13) | ||||
CVE-2022-22806 | 1 Schneider-electric | 16 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 13 more | 2024-11-21 | 9.8 Critical |
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause an unauthenticated connection to the UPS when a malformed connection is sent. Affected Product: SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior) | ||||
CVE-2022-22805 | 1 Schneider-electric | 16 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 13 more | 2024-11-21 | 9.8 Critical |
A CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists that could cause remote code execution when an improperly handled TLS packet is reassembled. Affected Product: SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior) | ||||
CVE-2022-22804 | 1 Schneider-electric | 1 Ecostruxure Power Monitoring Expert | 2024-11-21 | 5.4 Medium |
A CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could allow an authenticated attacker to view data, change settings, or impact availability of the software when the user visits a page containing the injected payload. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior) | ||||
CVE-2022-22727 | 1 Schneider-electric | 1 Ecostruxure Power Monitoring Expert | 2024-11-21 | 8.8 High |
A CWE-20: Improper Input Validation vulnerability exists that could allow an unauthenticated attacker to view data, change settings, impact availability of the software, or potentially impact a user�s local machine when the user clicks a specially crafted link. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior) | ||||
CVE-2022-22726 | 1 Schneider-electric | 1 Ecostruxure Power Monitoring Expert | 2024-11-21 | 6.5 Medium |
A CWE-20: Improper Input Validation vulnerability exists that could allow arbitrary files on the server to be read by authenticated users through a limited operating system service account. Affected Product: EcoStruxure Power Monitoring Expert (Versions 2020 and prior) | ||||
CVE-2022-22725 | 1 Schneider-electric | 2 Easergy P3, Easergy P3 Firmware | 2024-11-21 | 8.8 High |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P3 (All versions prior to V30.205) | ||||
CVE-2022-22724 | 1 Schneider-electric | 12 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 9 more | 2024-11-21 | 7.5 High |
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions) | ||||
CVE-2022-22723 | 1 Schneider-electric | 2 Easergy P5, Easergy P5 Firmware | 2024-11-21 | 8.8 High |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101) | ||||
CVE-2022-22722 | 1 Schneider-electric | 2 Easergy P5, Easergy P5 Firmware | 2024-11-21 | 7.5 High |
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could result in information disclosure. If an attacker were to obtain the SSH cryptographic key for the device and take active control of the local operational network connected to the product they could potentially observe and manipulate traffic associated with product configuration. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101) | ||||
CVE-2022-0715 | 1 Schneider-electric | 66 Scl Series 1029 Ups, Scl Series 1029 Ups Firmware, Scl Series 1030 Ups and 63 more | 2024-11-21 | 9.1 Critical |
A CWE-287: Improper Authentication vulnerability exists that could cause an attacker to arbitrarily change the behavior of the UPS when a key is leaked and used to upload malicious firmware. Affected Product: APC Smart-UPS Family: SMT Series (SMT Series ID=18: UPS 09.8 and prior / SMT Series ID=1040: UPS 01.2 and prior / SMT Series ID=1031: UPS 03.1 and prior), SMC Series (SMC Series ID=1005: UPS 14.1 and prior / SMC Series ID=1007: UPS 11.0 and prior / SMC Series ID=1041: UPS 01.1 and prior), SCL Series (SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior), SMX Series (SMX Series ID=20: UPS 10.2 and prior / SMX Series ID=23: UPS 07.0 and prior), SRT Series (SRT Series ID=1010/1019/1025: UPS 08.3 and prior / SRT Series ID=1024: UPS 01.0 and prior / SRT Series ID=1020: UPS 10.4 and prior / SRT Series ID=1021: UPS 12.2 and prior / SRT Series ID=1001/1013: UPS 05.1 and prior / SRT Series ID=1002/1014: UPSa05.2 and prior), APC SmartConnect Family: SMT Series (SMT Series ID=1015: UPS 04.5 and prior), SMC Series (SMC Series ID=1018: UPS 04.2 and prior), SMTL Series (SMTL Series ID=1026: UPS 02.9 and prior), SCL Series (SCL Series ID=1029: UPS 02.5 and prior / SCL Series ID=1030: UPS 02.5 and prior / SCL Series ID=1036: UPS 02.5 and prior / SCL Series ID=1037: UPS 03.1 and prior), SMX Series (SMX Series ID=1031: UPS 03.1 and prior) |