Filtered by vendor Rockwellautomation Subscriptions
Total 301 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2019-10954 1 Rockwellautomation 10 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 7 more 2024-11-21 7.5 High
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
CVE-2019-10952 1 Rockwellautomation 8 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compactlogix 5370 L1 and 5 more 2024-11-21 9.8 Critical
An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
CVE-2018-8843 1 Rockwellautomation 1 Arena 2024-11-21 N/A
Rockwell Automation Arena versions 15.10.00 and prior contains a use after free vulnerability caused by processing specially crafted Arena Simulation Software files that may cause the software application to crash, potentially losing any unsaved data..
CVE-2018-19616 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2024-11-21 N/A
An issue was discovered in Rockwell Automation Allen-Bradley PowerMonitor 1000. An unauthenticated user can add/edit/remove administrators because access control is implemented on the client side via a disabled attribute for a BUTTON element.
CVE-2018-19615 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2024-11-21 6.1 Medium
Rockwell Automation Allen-Bradley PowerMonitor 1000 all versions. A remote attacker could inject arbitrary code into a targeted user’s web browser to gain access to the affected device.
CVE-2018-19282 1 Rockwellautomation 2 Powerflex 525 Ac Drives, Powerflex 525 Ac Drives Firmware 2024-11-21 N/A
Rockwell Automation PowerFlex 525 AC Drives 5.001 and earlier allow remote attackers to cause a denial of service by crashing the Common Industrial Protocol (CIP) network stack. The vulnerability allows the attacker to crash the CIP in a way that it does not accept new connections, but keeps the current connections active, which can prevent legitimate users from recovering control.
CVE-2018-19016 1 Rockwellautomation 2 Ethernet\/ip Web Server Module 1756-eweb, Ethernet\/ip Web Server Module 1768-eweb 2024-11-21 N/A
Rockwell Automation EtherNet/IP Web Server Modules 1756-EWEB (includes 1756-EWEBK) Version 5.001 and earlier, and CompactLogix 1768-EWEB Version 2.005 and earlier. A remote attacker could send a crafted UDP packet to the SNMP service causing a denial-of-service condition to occur until the affected product is restarted.
CVE-2018-18981 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 N/A
In Rockwell Automation FactoryTalk Services Platform 2.90 and earlier, a remote unauthenticated attacker could send numerous crafted packets to service ports resulting in memory consumption that could lead to a partial or complete denial-of-service condition to the affected services.
CVE-2018-17924 1 Rockwellautomation 32 1756-en2f Series A, 1756-en2f Series A Firmware, 1756-en2f Series B and 29 more 2024-11-21 8.6 High
Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
CVE-2018-14829 1 Rockwellautomation 1 Rslinx 2024-11-21 N/A
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote threat actor to intentionally send a malformed CIP packet to Port 44818, causing the software application to stop responding and crash. This vulnerability also has the potential to exploit a buffer overflow condition, which may allow the threat actor to remotely execute arbitrary code.
CVE-2018-14827 1 Rockwellautomation 1 Rslinx 2024-11-21 N/A
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. A remote, unauthenticated threat actor may intentionally send specially crafted Ethernet/IP packets to Port 44818, causing the software application to stop responding and crash. The user must restart the software to regain functionality.
CVE-2018-14821 1 Rockwellautomation 1 Rslinx 2024-11-21 N/A
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote, unauthenticated threat actor to intentionally send a malformed CIP packet to Port 44818, causing the RSLinx Classic application to terminate. The user will need to manually restart the software to regain functionality.
CVE-2018-10619 1 Rockwellautomation 2 Factorytalk Linx Gateway, Rslinx Classic 2024-11-21 N/A
An unquoted search path or element in RSLinx Classic Versions 3.90.01 and prior and FactoryTalk Linx Gateway Versions 3.90.00 and prior may allow an authorized, but non-privileged local user to execute arbitrary code and allow a threat actor to escalate user privileges on the affected workstation.
CVE-2017-9312 1 Rockwellautomation 2 Allen-bradley L30erms, Allen-bradley L30erms Firmware 2024-11-21 N/A
Improperly implemented option-field processing in the TCP/IP stack on Allen-Bradley L30ERMS safety devices v30 and earlier causes a denial of service. When a crafted TCP packet is received, the device reboots immediately.
CVE-2017-6015 1 Rockwellautomation 1 Factorytalk Activation 2024-11-21 N/A
Without quotation marks, any whitespace in the file path for Rockwell Automation FactoryTalk Activation version 4.00.02 remains ambiguous, which may allow an attacker to link to or run a malicious executable. This may allow an authorized, but not privileged local user to execute arbitrary code with elevated privileges on the system. CVSS v3 base score: 8.8, CVSS vector string: (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H). Rockwell Automation has released a new version of FactoryTalk Activation, Version 4.01, which addresses the identified vulnerability. Rockwell Automation recommends upgrading to the latest version of FactoryTalk Activation, Version 4.01 or later.
CVE-2017-16740 1 Rockwellautomation 12 1766-l32awa, 1766-l32awa Firmware, 1766-l32awaa and 9 more 2024-11-21 N/A
A Buffer Overflow issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers, Series B and C Versions 21.002 and earlier. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution.
CVE-2017-14473 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2024-11-21 N/A
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Reads the encoded ladder logic from its data file and print it out in HEX.
CVE-2017-14472 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2024-11-21 N/A
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Requests a specific set of bytes from an undocumented data file and returns the ASCII version of the master password.
CVE-2017-14471 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2024-11-21 N/A
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
CVE-2017-14470 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2024-11-21 N/A
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.